Background Image
Previous Page  67 / 88 Next Page
Information
Show Menu
Previous Page 67 / 88 Next Page
Page Background

67

WWW.7X24EXCHANGE.ORG

circulation. regardless of the airflow

management effectiveness in the

data center, the it equipment airflow

temperature rise will be the

constant

1

.

table 1 charts the fixed relationship

between airflow, temperature

differential and heat within the data

center. the following equation is

used to establish these values:

Δt = 3.1W ÷ cfM

in this forMula:

• 3.1 is a constant coefficient at sea level

• W = watts

• CFM = cubic feet per minute airflow

the coefficient changes for

calculations at higher altitudes and in

Celsius, for airflow measurements in

liters per second or cubic meters per

hour, and for heat measured in kw or

btu. regardless of the unit of

measure being considered, there is a

fixed relationship between these

three factors. in practicable

applications, the Δt across it

equipment typically ranges from

around 20˚f up to around 35˚f,

depending on the type of

equipment. for example, blade

servers typically produce a higher Δt

than traditional rack mount servers.

Commonly Known

ΔT: Through

Cooling units

(#3 in Figure 1)

the other established data center Δt

occurs across cooling units. ideally,

this delta should be the same as the

delta across the it equipment,

indicating that the cooling resource

is in sync with the heat load it serves.

unfortunately, due to several factors

this is rarely the case. in legacy

direct expansion (dX) CraC units,

there is typically little allowance for

variation from baseline Δt. for

example, increases in return air

temperature often result in an

associated increase in supply air

temperature, so a 5˚f increase in

return air temperature might result in

a 3˚f or 4˚f increase in the supply

temperature. this results in the

overall Δt increasing slightly, but

nowhere near the proportion

possible with water-cooled coils.

Modern water-cooled Crah units

can remove heat equivalent from a

45˚f to 65˚f temperature drop across

the cooling coils. Given the

mathematical relationship between

heat, airflow and Δt previously

discussed (CfM = 3.1w/Δt), the

higher Δt across those coils equates

to removal of more heat, which

results in the Crah unit operating

much more efficiently. under most

circumstances increased efficiency is

welcome. however, if the Δt across

the it load is still only 20˚f, then

excess heat is not effectively being

removed. instead, the inefficiency of

the overall airflow management

scheme is being accommodated,

which is only a short-term solution.

the Δt across the cooling source is

also affected by set points. for

example, if there is a great deal of

bypass airflow in the data center, it is

possible that the return air can

actually be below the set point and

therefore returned to the data center

without any additional heat being

removed (Δt = zero). further, with a

standard return set point established

(similar to a home or office

thermostat setting), the Crahs will

be working to bring the data center

temperature down to that set point,

resulting in Δt’s which could range

from 0˚f to over 20˚f. finally, if the

Crahs are operating with a fixed

supply temperature, the Δt could

range from 20˚f to 35˚f based on the

types of servers deployed in that

space or the cooling coils could see

less than 10˚f if there is wasted

surplus cooling in the space (up to

over 40˚f if there is a cumulative hot

air re-circulation effect).

The less Commonly

Known DelTa T’s

beyond these well-established Δt’s,

there remains two hidden areas of

Δt that can help data center

owner/operators understand the

differences between it and cooling

coil Δt’s and suggest possible

remediating strategies. these are:

from cooling unit to front of it

equipment (#4 in figure 1) and from

exhaust back to cooling unit (#2 in

figure 1).

often ignored ΔT:

from Cooling unit

to front of iT

equipment

(#4 in Figure 1)

the Δt between the cooling unit

supply output and the server inlet is

Table 1: Relationship between airflow and ΔT